The single most demanding building-systems problem in a cancer center's pharmacy is containing the antineoplastic (chemotherapy) drugs it compounds. USP General Chapter <800> Hazardous Drugs — Handling in Healthcare Settings governs how those rooms are built, pressured, and exhausted, and it is the design driver that distinguishes an oncology pharmacy from any other hospital pharmacy.

USP <800> sets the facility envelope for compounding hazardous drugs

USP <800> is the controlling standard for receiving, storing, compounding, and disposing of hazardous drugs (HDs) across the healthcare enterprise — not just the cleanroom. It works in tandem with USP <797> (sterile compounding) and USP <795> (nonsterile compounding): <797>/<795> establish the cleanliness and sterility requirements, while <800> overlays the containment requirements specific to drugs on the NIOSH Hazardous Drug List. For a designer, <800> is what makes the rooms negative, exhausted, and segregated.

A few framing points that shape every design decision:

Hazardous drugs are compounded inside primary engineering controls

The drug is never open to the room air of even a negative room. It is manipulated inside a Primary Engineering Control (PEC) — a ventilated cabinet that captures contaminant at the point of generation and exhausts it. The two PEC families an oncology pharmacy uses:

The PEC sits inside a room — the Secondary Engineering Control (SEC) — and the combination of the two, plus containment practices and PPE, is what <800> calls containment. Critically, a PEC alone is not sufficient for antineoplastic sterile compounding: it must be housed in a properly pressurized, exhausted, ISO-classified room.

The room (SEC) must be negative pressure, externally exhausted, and ISO-classified

The Secondary Engineering Control is the buffer room (and its anteroom) that contains the PEC. For HD sterile compounding the SEC must simultaneously satisfy <800> containment and <797> cleanliness:

Parameter Typical requirement (rule-of-thumb)
Room pressurization Negative relative to adjacent spaces — commonly cited around −0.01 to −0.03 in. w.c.
Air changes per hour (ACH) ≥ 30 ACH for the ISO 7 HD buffer room (the PEC's own HEPA-filtered airflow contributes to total)
Air cleanliness ISO Class 7 buffer room; ISO Class 7 (or better) anteroom serving negative-pressure HD areas
Exhaust 100% exhausted to the outside — no recirculation of HD-area air back into the building
HD storage HDs requiring refrigeration stored in a dedicated refrigerator in a negative-pressure room, with ≥ 12 ACH; the negative-pressure storage room is also externally exhausted

Key design consequences: